EasyManua.ls Logo

Riello NXC 021 - Active Setpoint Configuration; Capacity Control Mechanism

Riello NXC 021
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
91
PRO-DIALOG+
EN
3.5.4 Pump control
The control is able to manage one or two pumps
inside
the unit. The pump is activated if the spe-
cic
parameter is congured (PUMPCONFIG)
and if the unit is in heating or cooling mode.
Thestart-updelayvalueofthecompressor,withrespectto
thepump,issetto1minute(default)butitcanbeextended
to15minutes.Inthiscasethepumpwillworkwithcompres-
sorstoppedforatimeequaltothesetdelayvalue.
If the unit stops the pump stays ON for 20 seconds.
However, if the unit changes mode (heating/cooling), the
pump carries on working. The pump instead stops if the
unitisinlockoutconditionduetoanerror,unlessthean-
ti-freezeprotectionistriggered.Moreover,itcanbestarted
iftheelectricheatingelementoftheplateexchangeristrig-
gered.Refertothespecicparagraphforpumpcontrolde-
tailsincaseofinstallationoftwomachinesinMaster/Slave
conguration.
3.5.5 Control point
The control point is the water temperature value that the
unitmustreach.Theexchangerenteringwatertemperature
isalreadysetwhiletheleavingtemperaturecanbeset,ho-
weveronlybytheTechnicalSupportService.Thecontrolpoint
valueiscalculatedas:
Control point: Active setpoint +Reset
3.5.6 Active setpoint
Uptotwosetpointscanbeselectedincoolingmodeandtwo
inheatingmode.Usually,thesecondvalueismatchedtope-
riodsinwhichtheunitisnotactive.
Thisvaluecanbeselected:
• fromthecontrolpanel(GENUNITmenu).
• fromdrycontacts
from CCN
through timer setting
Thetablesbelowlisttheselectionsavailableaccordingtothe
controltype(frompanelorinremote).Theparameterslisted
are:
• Local setpoint selection: the value to be entered
is in the GENUNIT menu, LSP_SEL parameter.
• Timeschedule2:SelecttheSCHEDULEsub-menutoaccess
the CONFIG menu.
• Setpointselectioncontact:thisparameteridentiescon-
tactstatus(openorclose).
Heating / cooling
operation mode
Local
setpoint
selection
Calendar 2
status
Active setpoint
Cooling sp 1 - Cooling setpoint 1
Cooling sp 2 - Cooling setpoint 2
Cooling auto occupied Cooling setpoint 1
Cooling auto unoccupied Cooling setpoint 2
Heating sp 1 - Heating setpoint 1
Heating sp 2 - Heating setpoint 2
Heating auto occupied Heating setpoint 1
Heating auto unoccupied Heating setpoint 2
OPERATING MODE: FROM CONTROL PANEL
PARAMETER STATUS
Heating / cooling
operation mode
Contact setpoint
selection
Active setpoint
Cooling sp1(open) Cooling setpoint 1
Cooling sp2(closed) Cooling setpoint 2
Heating sp1(open) Heating setpoint 1
Heating sp2(closed) Heating setpoint 2
OPERATING MODE: REMOTE PANEL
PARAMETER STATUS
3.5.7 Reset
The Reset parameter aim is to change the active setpoint va-
lue(incoolingmodeitincreasesthevaluewhileinheating
modeitdecreasesit)inordertoreducethecapacityreque-
sted to the machine. The change of this value is a conse-
quenceofadropoftheoutsidetemperaturevalueordrop
of the temperature differential in the plate exchanger and
isaimed atimprovingmachineperformance.As onemight
noticefromthegraphbelow,theresetvalueisacurvewhere
thevaluescanbesetfromthecontrolpanelbyaccessingthe
RESETCFGmenu.Parameterstobesetarethefollowing:
Maximumresetvalue(A)
Outside temperature value (or variation of
exchangertemperature)forwhichtheresetvalueis=0(B)
Outside temperature value (or variation of
exchangertemperature)forwhichtheresetvalueisma-
ximum(C)
Exampleofresetvaluetrendwithunitincoolingmode.
3.5.8 Demand limitation
Thisfunctionisusedtolimitunitpowerconsumption.Basically,
theunitcannotexceedasetpointlimitvaluethatcanbesetfrom
the control panel accessing the SETPOINT menu. In this case,
thedrycontactswillbeused.
3.5.9 Capacity control
With this function, the machine adjusts the compres-
sor so that the temperature of the exchanger leaving wa-
ter is kept to the set value (setpoint). The control pa-
nel constantly measures the temperature of the unit
entering and leaving water as well as the difference
oftemperaturewiththesetpoint.Basedonthereadvalues,
itdecidestochangemachinecapacitybyactingonthecom-
pressor.Ifthecompressorisstartedtoofrequentlyoriskept
Reset value
Outdoor temperature (OAT)
Heat exchan
g
er delta T
% Building load
A
°C
3
100
D
B
C
10
3.0
20
5.0
°C0
%

Table of Contents

Related product manuals