EasyManua.ls Logo

Riello NXC 021 - Unit Maintenance Checks; Refrigerant Volume Check

Riello NXC 021
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
97
Alarm codes
EN
6.1 ALARM MENU
The
Pro-Dialog+
panel features many troubleshooting
functions. In case of error, an alarm will be triggered and
its identicationcodewill beloggedintothealarm menu,
CUR_ALRMandALARMRSTsub-menus.
ThecontrolpanelLEDswillsignalthealarms.Itisreminded
that:
• ashing LED indicates that at least one circuit of the
machine
isinoperationbutthereisawarningsituation.
• steadyLEDindicatesthatatleastonecircuitofthemachi-
ne
hasstoppedduetoanerror.
ALARMRST sub-menu shows up to ve alarm codes active
withintheunit.
6.3 ALARM CODES
Alarm
number
Alarm code Alarm description Reset mode Probable cause Control system reaction
Thermistor faults
1 th-01 Heatexchangerenteringwatertemperature
sensor fault
Automatic,whenthe
temperaturedetectedisback
to normal again
Thermistor fault Unit stop
2 th-02 Heatexchangerleavingwatertemperature
sensor fault
As above As above As above
3 th-03 Defrost fault of cooling circuit A As above As above Stopofthecircuitifthedeviceis
inheatingmode
4 th-04 DefrostfaultofcircuitBorsecondfaultof
circuit B sensor
As above As above As above
5 th-10 Outdoortemperaturesensorfault As above As above Unit stop
6 th-11 CHWS sensor fault
(Master/Slave)
As above As above Stop of the Master/Slave operation
mode
7 th-12 Circuit A suction sensor fault As above As above Stop of the circuit
8 th-13 Circuit B suction sensor fault As above As above As above
9 th-44 Faultofsuctionsensor,heatexchanger1 As above As above As above
10 th-45 Faultofsuctionsensor,heatexchanger2 As above As above As above
Pressure transducer faults
11 Pr-01 DeliverypressuretransducerAfault Automatic,whenvoltageis
backtonormal
Transducerfaultor
installation error
Stop of the circuit
12 Pr-02 DeliverypressuretransducerBfault As above As above As above
13 Pr-04 CircuitAsuctionpressuretransducerfault As above As above As above
14 Pr-05 CircuitBsuctionpressuretransducerfault As above As above As above
51 Pr-24 Pressuresensorfaultatwaterinlet Automatic,whenthevalueof
thevoltagetransmittedbythe
sensorisbacktonormal
Sensor fault or
installation error
Stop of the circuit
52 Pr-25 Pressuresensorfaultatwateroutlet As above As above As above
Communication with slave boards
15 CO-BB CommunicationlosswithNRCP2board Automatic,when
communications have been
restored
Communication bus
installation error or
slaveboardfault
Compressor A3 or circuit B stop,
accordingtoconguration
16 Co-ht Communicationlosswiththeboardfor
additionalheatingsteps
As above As above Stopofadditionalheatingsteps
17 Co-e1 CommunicationlosswithEXVvalveboard As above As above Unit stop
18 Co-o1 CommunicationlosswithPD-AUX1board As above As above Device stop if equipped with
optionalwaterpressuresensor
6.2 ALARM RESET
Once the error is solved, the alarm code
must be reset. Reset procedure can
bemanualorautomatic,dependingonthetypeofcodeof
alarm. Alarm reset can be carried out al-
so
with machine running. In case of power blackout
the
unitwillautomaticallyrestartwithouttheenablingre-
questfromthecontrolpanel.
Nevertheless,ifthemachine,duringthisinterruption,regi-
sters
somealarms,theycaninhibittheautomaticrestart.
The manual resetprocedure of the alarms must be carried
outfromtheALARMRSTmenu,RST_ALMparameter.However,
accesstothisparametercanbeprotectedbyapassword(that
canbeconguredfromtheGENCONFmenu).

Table of Contents

Related product manuals