PRO-DIALOG+
92
EN
runningforlessthanaminutethesystemautomaticallyre-
ducesthenumberofstart-upsbutinthiscasethecontrolon
the setpoint temperature is less effective.
Start-upscanbeinuencedbytheinterventionofotherfun-
ctions
suchasdefrost.
3.5.10 Night mode
Thisfunctionlimitsmachinecapacityoverasetperiodofti-
me. The period is set by accessing the GENUNIT menu and
simplysettingastartandnishtime.Usuallyitissetforthe
night time.
3.5.11 Control of optional electric heating elements
NXH units can manage up to four optional electric hea-
ting elements. Heating elements activate to compensate
the heat request to the machine in particular under these
conditions:
•
When the unit is already at its full capacity or when
itscapacityisreducedduetothetriggeringofsomesafety
devices
• The outside temperature value is lower than the
setthresholdvalue(HCCONFIGmenu)
• The demand limit function has not been activated.
Incasemorethanoneheatingelementisused,thelastone
couldbeutilizedasbackup,whichcanbeactivatedincase
of machine fault, supporting the other heating elements.
3.5.12 Desuperheater option
In units equipped with desuperheater it is possi-
ble to recover the heat from the hot water. The op-
tion is activated from the SETPOINT menu by setting
the min_sct parameter. It is also possible to use the
drycontacts(seeinputsMENU,DSHTR_SWparameter).
3.5.13 Defrost function
It is a function present also in the NXH series machines.
It is activated when the unit is in heating mode to pre-
vent the formation of ice on the air side exchanger.
Thedefrostcycleisperformedononelineatatime(in
caseofmachineswithtwoormorelines);duringthedefrost
phasethefanofthelineundergoingthecyclewillstopand
thefour-wayvalvewillinvertthecycleforcingthemachine
to
operateincoolingmode.Defrostcycle
isautomaticanddoesnotrequireanysetting.
3.5.14 Control of an auxiliary boiler
Thisfunction,aswellasthecontroloftheelectricheating
elements,isnotpossibleifthemachineisconguredas
Slave.
NXH units can manage an alternative source of heat such as a
boiler,bycontrollingitsstart-up.Whentheboilerisinope
-
rationtheunitisstopped.
Boilercanbeactivatedwhen:
• The unit is in heating mode but it is stopped due toan
error.
• Theunitisinheatingmodebuttheoutdoorairtempera
-
ture
istoolow.Usually,thesetthresholdvalueis-10_Kbut
itcanbeconguredfromtheHCCONFIGmenu.
3.5.15 Master/Slave unit
Two ProDialog+ can be connected together in a Master-
Slave unit system. The two controls communica-
te
through the CCN bus. Conguration parameters are
accessible
onlyfromthe SERVICE menu requiring the inter-
vention of the Technical Support Service.
The
Master-Slavesystemrequiresacascadingprobeforeach
machinetobeconnectedtothepipingcomingoutofthesystem.
The
systemcanmanagepumpswithxedandvariableow
rate;forunitswithvariableowratepump,eachunitcon-
trols
itspumpaccordingtotherequiredload.
Ifxedowratepumpsareusedinstead,thesearealways
runningevenwhenthesystemhasaloadrequest.Itispos-
sible
tohavetheMasterunittomanageonesystempump:in
thiscasetheSlavemachinepumpisnotused.
AllchecksandsettingswillbeperformedontheMasterma-
chine
thatwilltransmittheinformationtotheSlave.
TheMastercanbecontrolledfromtheunitpanel,remotepa-
nel
or CCN system. If the Master is controlled from remote
panel,usedrycontactstoturnsystemonandoff.
One of the Master-Slave functions allows establishing
not only which one is the Master and which one is the
Slave unit, but also inverting the roles if the operating
hours of the two units are a lot different. The system, if
congured,
willtrytokeeptheoperatinghoursofbothma-
chines
identical.
Shouldthesystemnotbeconguredasdescribedabove,the
machinechosenasMasterwillalwaysremainthatway.The
Mastermachinealwaysstartsrst,untilitreachesitsfullca
-
pacity.
Now a countdown starts for the Slave machi-
ne
that will be started once countdown is over.
The water setpoint used by the Slave machine is
the same of the Master machine.
During
cascading operation, the Master will always
work to its full capacity if the Salve is running, other-
wise
it can modulate its operation according to the
system
request. In case of communication error
between
MasterandSlave,thetwounitswillcarryonwor-
king
asseparatemachines,usingtheprogrammingsetfrom
each control panel.
IftheMastershutsdownduetoanerror,thentheSlavewill
startregardlessoftheMasterenablingsignal.
ForNXHmachinesinMaster-Slavecongurationorequip
-
pedwithatleastoneadditionalelectricheatingelement,
thecontrolmustbeontheenteringwatertemperature.