0 0
181 / 0 / -180
27
ACTIVE POWER SUM
29
APPARENT POWER SUM
31
REACTIVE POWER SUM
32
POWER FACTOR AVG
34
PHASE ANGLE AVG
36
FREQUENCY
0 - 120 %
0 - 120 %
0 - 120 %
43
WATT DEMAND IMPORT
44
WATT MAX DEMAND IMP.
45
WATT DEMAND EXPORT
46
WATT MAX DEMAND EXP.
0 - 120 %
0 - 120 %
0 - 120 %
0 - 120 %
Sr.
No.
Parameter
3P 4W
1P 2W
3P 3W
Range
Analog Output Limit Output
10 - 120 %
10 - 120 %
10 - 120 %
10 - 100 %
10 - 120 %
10 - 120 %
10 - 120 %
10 - 120 %
(1)
10 - 100 %
(2)
10 - 100 %
(2)
0 0
181 / 0 / -180
45 to 66 Hz
51
VA DEMAND
52
VA MAX DEMAND
53
CURRENT DEMAND
54
CURRENT MAX DEMAND
101
INPUT VOLTAGE L12
102
INPUT VOLTAGE L23
103
INPUT VOLTAGE L31
113
NEUTRAL CURRENT
0 - 100 %
0 - 100 %
0 - 100 %
0 - 100 %
0 - 120 %
0 - 120 %
0 - 100 %
0 - 100 %
10 - 120 %
10 - 120 %
10 - 120 %
10 - 120 %
10 - 120 %
10 - 120 %
10 - 120 %
10 - 120 %
Note : Parameters 1,2,3 are L-N Voltage for 3P 4W & L-L Voltage for 3P 3W .
(1) For Frequency 0% corresponds to 40 Hz & 120% corresponds to 70 Hz.
(2) For Angle and PF 0% corresponds to 0 Deg. & 100% corresponds to 360 Deg.
8. Relay output (Optional) :
This is provided with either 1 or 2 relay for pulse output as well as for limit switch instrument
8.1 Pulse Output :
Pulse output is the potential free, very fast acting relay contact which can be used to drive
an external mechanical counter for energy measurement.
51