EasyManua.ls Logo

Rittal Blue e+ - Page 31

Rittal Blue e+
52 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Rittal roof-mounted Blue e+ cooling unit/VX25 Blue e+ integration solution 31
7 Operation
EN
Change unit
All temperature values for the unit may be displayed ei-
ther in degrees Celsius "°C" or degrees Fahrenheit "°F".
Click on the "Change unit" symbol.
Change the required unit ("°C" or "°F") using the "Up"
or "Down" arrows.
Confirm your entry with "OK".
Control mode
The cooling unit controls cooling output according to
one of the following three temperature values:
Inside temp.: The temperature at which air is drawn
out of the enclosure into the cooling unit.
External sensor: The temperature measured with an
external temperature sensor at a so-called hot spot in
the enclosure.
Outlet temp.: The temperature measured with an ex-
ternal temperature sensor at the cold air outlet from
the cooling unit.
Control mode "external sensor"
Please observe the following when selecting the sensor
position: The sensor must not
be influenced directly by the cold air expelled from the
cooling unit,
be influenced by external heat sources or heat radia-
tion,
be exposed to humidity,
have its connection cable laid in the vicinity of AC ca-
bles,
be exposed to different temperature levels within the
first 10 cm of the connection cable.
The sensor must
be located within the effective range of the cooling
unit,
be surrounded by adequate moving air which has
blended well with the air expelled by the cooling unit,
be at an adequate distance from solid and liquid sub-
stances.
Control mode "outlet temperature"
Attach the temperature sensor in front of the cold air
outlet from the cooling unit, in the centre (fig. 20).
Fig. 20: Temperature sensor in front of cold air outlet
Key
1 Temperature sensor
2 Cold air discharge at the bottom of the unit
Selecting a control mode
Click on the "Control mode" symbol.
The setpoint for the currently set control mode is dis-
played.
Choose your preferred control mode by selecting it
from the display:
The corresponding symbol for the chosen control mode
is likewise displayed on the overview page.
Symbol Parameter
Change unit
Set the unit "°C" or "°F"
Control mode
Alarm threshold
Temperature limit which will trigger an alarm
message if exceeded.
Tab. 13: "Temperature" zone
Note:
The sensor element must not be in contact
with the enclosure.
Note:
To ensure the accuracy of the outlet temper-
ature, at least 50% of the total cooling output
should be installed as heat loss. The output
can be taken from the characteristic curve for
this unit.
Symbol Parameter Setpoint Factory
setting
Internal
temperature
20 °C (68 °F)
50 °C
(122 °F)
35 °C (95 °F)
External
sensor
Outlet
temperature
18 °C (64 °F)
28 °C (82 °F)
24 °C (75 °F)
Tab. 14: "Control mode" zone
1
2

Table of Contents

Related product manuals