- 59 -
13
11. Product Specifications
Model SP-220(TYPE F)
Single channel (R600a:Refer to "Gas list")
Depends on the measured gas
(R600a
Triggered when the concentration of detected gas reaches
or exceeds the alarm setpoint value.
Sensor connection/disconnection, low battery, low flow rate,
circuit abnormality, calibration range abnormality, clock
abnormality and pump abnormality
Lamp blinking and intermittent buzzer sounding
Lamp blinking, intermittent buzzer sounding and fault detail
(*R600a:10ppm,30ppm,150ppm,500ppm,2000ppm
other gases: refer to “Gas list”)
Within 30 seconds of 10ppm alarm by contact with R600a: 1800ppm
Display contents: Gas name, gas concentration (scale + bar display), time,
battery level, drawing, operation and mode
Continuous
operating time
13 hours or more (normal temperature, without alarms or lighting)
Operating temperature range: -20 - +55ºC
Operating humidity range: 95%RH or less (Non-condensing)
Approx. 43 (W) x 200 (H) x 39 (D) mm (projection portions excluded)
Approx. 215 g (without batteries)
Explosion-proof
structure
Intrinsically safe explosion-proof structure
ExiaIICT4(TIIS)/II1GExiaIICT4Ga(Presafe/ATEX)(IECEx)
LCD backlight (automatically lights up in response to an alarm), Data logger,
Log data display, Peak hold, Clock display, Changing a reading target gas
2 AA alkaline dry batteries, Hand strap, Rubber protection cover,
Waterproofing filter for exchange (5 pcs), Taper nozzle
The gas concentration is only approximate because the detector is designed to be used to detect a small
amount of gas leakage.