Rockwell Automation Publication 1766-UM001O-EN-P - September 2021 205
Appendix F MicroLogix 1400 Distributed Network Protocol
Maximum Error Count in Secure Authentication
This parameter is supported only in MicroLogix 1400 Series B and Series
Controllers.
This parameter is used for configuring the maximum error count.
The valid range is 0…10. Default value is 2.
HMAC Algorithm in Secure Authentication
This parameter is supported only in MicroLogix 1400 Series B and Series C
controllers.
This parameter is used for configuring the HMAC Algorithm.
• 1 = HMAC SHA-1 truncated to 4 octets (serial)
• 2 = HMAC SHA-1 truncated to 10 octets (networked)
• 3 = HMAC SHA-256 truncated to 8 octets (serial)
• 4 = HMAC SHA-256 truncated to 16 octets (networked)
The valid range is 1…4. Default value is 2.
User Info Config File Number in Secure Authentication
This parameter is supported only in MicroLogix 1400 Series B and Series C
controllers.
This file number is used to define user information Secure Authentication.
The value of this parameter is N file only. Valid range is 0, 7, 9…255. Default
value is 0.
In RSLogix 500/RSLogix Micro software, when this parameter is configured
properly, you can see a DNP3 Auth User Info Config File tree in Channel
Configuration.

Table of Contents

Other manuals for Rockwell Automation 1766-L32BWAA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation 1766-L32BWAA and is the answer not in the manual?

Rockwell Automation 1766-L32BWAA Specifications

General IconGeneral
BrandRockwell Automation
Model1766-L32BWAA
CategoryController
LanguageEnglish

Related product manuals