Publication 2711C-UM001C-EN-P - September 2009 81
Troubleshoot the System Chapter 6
Communication 8 Communication Server Error. Contact technical support providing this data.
ID1-/*S:0 Param1*/, ID2-/*S:0 Param2*/, P1-/*S:0
Param3*/, P2-/*S:0 Param4*/, P3-/*S:0 Param5*/,
P4-/*S:0 Param6*/, P5-/*S:0 Param7*/, P6-/*S:0
Param8*/
Reboot the terminal.
Communication 9 Communication Server Error. Contact technical support providing this data.
ID1-/*S:0 Param1*/, ID2-/*S:0 Param2*/
Reboot the terminal.
Communication 10 Write Error for Alias /*S:0 Param2*/, Controller
/*S:0 Param3*/, Address is /*S:0 Param4*/,
Communication Flag is /*S:0 Param1*/
The terminal is having trouble writing the external
tag at this controller and address.
Verify you have good communication to the
controller.
Verify that the communication network cable is
connected.
If new ladder logic is downloading to the controller,
you could see this message. After the download,
communication should run normally.
If a remote device not responding alert is present,
then all external tags being written to will generate
this alert.
Is the address configured in the controller? If the
address is configured as read only at the controller,
this address can not be written to. Set this external
tag as read and remove panel devices from your
application that can write data to this external tag.
Communication 11 Read Error for Alias /*S:0 Param2*/, Controller
/*S:0 Param3*/, Address is /*S:0 Param4*/,
Communication Flag is /*S:0 Param1*/
The terminal is having trouble reading the external
tag at this controller and address.
Verify you have good communication to the
controller.
Verify that the communication network cable is
connected.
If new ladder logic is downloading to the controller,
you could see this message. After the download,
communication should run normally.
If a remote device not responding alert was
present, then all external tags being read from will
generate this alert.
Is the address configured in the controller? If the
address is configured as write only at the
controller, this address can not be read from. Set
this external tag as write and remove panel devices
from your application that can read data from this
external tag.
PanelView Component Terminal Alerts
Category ID Description Corrective Action