Chapter 1 Store and Load a Project By Using a
Memory Card
Rockwell Automation Publication 1756-PM017J-EN-P - March 2022 15
Prerequisites
Make all the required edits to the logic.
Download the project to the controller.
Schedule your ControlNet networks.
To store a project
1. Go online with the controller.
2. Put the controller in Program Mode (Rem Program or Program).
3. On the Online toolbar, select the Controller Properties icon.
Tip: For 1756-L7
x
controllers only,
Energy Storage
instead of
Battery OK
appears beside the
Controller
Properties
icon. Refer to the
ControlLogix System User Manual
, publication
1756-UM001 available at
http://literature.rockwellautomation.com/idc/groups/literature/documents/um/1756-um001_
-en-p.pdf, for information on the Energy Storage Module.
4. On the Controller Properties dialog box, select the Nonvolatile
Memory tab and then select Load/Store.
IMPORTANT
At the bottom of the Nonvolatile Memory tab, a message appears if the
CompactFlash card or SD card is empty.
A message also appears if the SD card is locked.
5. At the bottom of the Nonvolatile Memory tab, select Inhibit Automatic
Firmware Update checkbox if you do not want to automatically store
an image during a Save or Load operation.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation Logix 5000 Series and is the answer not in the manual?

Rockwell Automation Logix 5000 Series Specifications

General IconGeneral
BrandRockwell Automation
ModelLogix 5000 Series
CategoryController
LanguageEnglish

Related product manuals