Chapter 1 Store and Load a Project By Using a
Memory Card
16 Rockwell Automation Publication 1756-PM017J-EN-P - March 2022
6. Choose when (under what conditions) to load the project back into the
user memory (RAM) of the controller.
Description
The project that is currently on the memory card of the controller (if any project is there).
The project that is currently in the user memory (RAM) of the controller.
Store operation.
In the Load Image field, if you choose On Power Up or On Corrupt
Memory, you must also choose the Load Mode you want to controller
to go to after the load.
Remote Program
Remote Run
7. In the Automatic Firmware Update list, use the default (disable) or
choose the appropriate Firmware Supervisor.
For details on the Firmware Supervisor options, see the ControlLogix
System User Manual, publication 1756-UM001 available at
http://literature.rockwellautomation.com/idc/groups/literature/docu
ments/um/1756-um001_-en-p.pdf.
8. Select <-- Store.
IMPORTANT
Store is not active if the SD card is locked.
A dialog box asks you to confirm the store operation.
9. To store the project, select Yes.