40 of 136
4. Use the down arrow key to highlight ‘Set Defaults’ if necessary and press the Enter key located in the
center of the HIM keypad to make this your selection.
5. The screen which follows after completion of the previous step is shown. Use the down arrow key to highlight
‘This Port Only’. Press the Enter key located in the center of the HIM keypad to make this your selection.
ESC INFO
Port 00 Set Defaults
Host and Ports ( Preferred)
This Port Only
6. Use the soft key labeled ‘ALL’ to reset default all parameter settings in the Drive.
W A R N I N G
Use MOST to reset typical
settings on this port
(preferred). Use ALL to
reset all settings
ALL MOST
7. Use the ‘CLR’ soft key to acknowledge and clear the ‘Module Defaulted’ fault.
Press the ‘Enter’ soft key.
8. Press the ‘Folders’ button on the HIM keypad again to access the Folders Menu.