Edit Speed Units
RPM
1
0
1
Startup
Reference Selection
Def
Min
Max0
Setting the Speed Feedback Device
26. With the completion of the previous step, you have finished inputting the Motor Nameplate data and other information
required in the ‘Motor Data’ section. Pressing the ‘ENTER’ soft key in the previous step has directed you to the Main
Menu and the item ‘Feedback’ should be highlighted. Press the ‘ENTER’ soft key to make this your selection.
ABORT ENTER
General Startup
Motor Control
Motor Data
Main Menu
Limits
Complete these steps in order:
Feedback
27. Select ‘Open Loopas we do not have an encoder on board the Drive.