EasyManua.ls Logo

Roger PRT12EM - Page 29

Default Icon
54 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
PRTxxEM series readers Operating Manual.doc 2018-08-21
29/54
[63][S][KL] Programming AUX1 Timer, S=0..1, KL=00..99, default: S=0, KL=02
The AUX1 Timer defines triggering time for AUX1 Momentary output. When S=0 and KL=00
then output will be triggered indefinitely until the reader’s arming mode is switched. Program S=0
for seconds or S=1 for minutes. Setting S=1 and KL=00 is forbidden.
[64][S][KL] Programming AUX2 Timer, S=0..1, KL=00..99, default: S=0, KL=02
The AUX2 Timer defines triggering time for AUX2 Momentary output. When S=0 and KL=00
then output will be triggered indefinitely until the reader’s arming mode is switched. Program S=0
for seconds or S=1 for minutes. Setting S=1 and KL=00 is forbidden.
[65][J] Programming option Enable Card/PIN reading when Prealarm”, J=0..1,
default: J=0
When J=0 then the option is disabled and reader will not read cards nor PIN-s when it is in
Prealarm state, when J=1 reader will allow to use cards/PIN-s during Prealarm state.
[66][J] Programming option “Unlimited duration of Door Ajar alarm”, J=0..1, default:
J=0
When J=0 then Door Ajar alarm will be automatically cleared after 3 minutes or immediately with
valid card/PIN entered. When J=1 then Door Ajar will last as long as door is opened.
[67][EF] Programming function for built-in REL1 output, EF=11, 41..64, default:
EF=46
This command sets the function for built-in REL1 output. The list of functions is give in section 8.1.
[68][S][KL] Programming Tamper Timer, S=0..1, KL=00..99, default: S=1 KL=60
This timer defines duration time for Tamper Alarm which can be signalled with [55] function
output. When S=0 and KL=00 then the alarm will be triggered indefinitely until the reader’s arming
mode is switched. Program S=0 for seconds or S=1 for minutes. Setting S=1 and KL=00 is
forbidden.
[69][S][KL] Programming Intruder Timer, S=0..1, KL=00..99, default: S=1 KL=60
This timer defines duration time for Intruder Alarm which can be signalled with [56] function
output. When S=0 and KL=00 then the alarm will be triggered indefinitely until the reader’s arming
mode is switched. Program S=0 for seconds or S=1 for minutes. Setting S=1 and KL=00 is
forbidden.
[70][S][KL] Programming General Alarm Timer, S=0..1, KL=00..99, default: S=1 KL=
03
This timer defines duration time for General Alarm which can be signalled with [57] function
output. When S=0 and KL=00 then the alarm will be triggered indefinitely until the reader’s arming
mode is switched. Program S=0 for seconds or S=1 for minutes. Setting S=1 and KL=00 is
forbidden.
[71][S][KL] Programming Door Unlock Time, S=0..1, KL=00..99, default: S=0 KL= 04
The KL digits define time (in seconds when S=0 or in minutes when S=1) for which the reader will
unlock a door when access is granted. When S=0 and KL=00 reader unlocks a door for unlimited
time. If reader operates with door open sensor (input [21]: Door Contact) door is automatically
re-locked when door sensor indicates corresponding door is closed again regardless of fact the
Door Unlock Time did not pass by. Setting S=1 and KL=00 is forbidden.
[72][S][KL] Programming Door Open Timeout, S=0..1, KL=00..99, default: S=0 KL=12
The KL digits define time (in seconds when S=0 or in minutes when S=1) for which door should be
closed otherwise Door Ajar alarm will be raised. The Door Open Timeout starts immediately
after Door Unlock Time is passed by. If the reader operates without door contact sensor then
Door Open Timeout is ignored and has no effect on reader’s operation. Setting S=1 and KL=00 is
forbidden.

Table of Contents