Quick Installation Guide
00825-0100-4663, Rev BC
December 2012
Rosemount 8732
29
NOTE
For intrinsically safe (IS) outputs on the 8732E output option code F must be selected.
IS outputs for Class I, Division 1, Groups A, B, C, D. Temp Code – T4 at 60°C
IS outputs for Ex de [ia] IIB or IIC T6
NOTE
For the 8732E transmitters with a local operator interface (LOI), the lower ambient
temperature limit is -20 °C.
North American Certifications
FM Approvals
N0 Non-incendive for Class I, Division 2
Groups A, B, C, and D non-flammable fluids
(T4 at 60 °C: -50 °C Ta +60 °C)
Dust-ignition proof Class II/III, Division 1
Groups E, F, and G (T5 at 60 °C)
Hazardous Locations; Enclosure Type 4X
N5 Non-incendive for Class I, Division 2,
Groups A, B, C, and D flammable fluids
(T4 at 60 °C: -50 °C Ta +60 °C)
Dust-ignition proof Class II/III, Division 1
Groups E, F, and G (T5 at 60 °C)
Hazardous Locations; Enclosure Type 4X
Requires sensors with N5 Approval
E5 Explosion proof for Class I, Division 1
Groups C and D (T6 at 60 °C)
Dust-ignition proof Class II/III, Division 1
Groups E, F, and G (T5 at 60 °C),
Non-incendive for Class I, Division 2
Groups A, B, C, and D flammable fluids
(T4 at 60 °C: -50 °C Ta +60 °C)
Hazardous Locations; Enclosure Type 4X
Canadian Standards Association (CSA)
N0 Non-incendive for Class I, Division 2
Groups A, B, C, and D non-flammable fluids
(T4 at 60 °C: -50 °C Ta +60 °C)
Dust-ignition proof Class II/III, Division 1
Groups E, F, and G (T4 at 60 °C)
Hazardous Locations; Enclosure Type 4X
4663RevBCQIG.fm Page 29 Thursday, January 10, 2013 5:33 PM