Controller Functionality
38 AYC-x6355 Installation and User Manual
passes. After this time, the door is locked even if the REX button
is not released.
Fail Safe Operation – From the moment the REX button is
pressed, the door is unlocked until the REX button is released,
plus the Lock Strike Release Time. In this case, the Lock Strike
Relay only begins its count down once the REX button is released.
8.8 Secure Application Appurtenances
Rosslare’s secure application appurtenances are designed for use with
Rosslare's secured series standalone access control units, including the
AYC-x6355 series. These units are designed to operate indoors and
installed within the secured premises. The units must be used with
one of Rosslare’s secure application appurtenances, which provide
Lock Strike output and REX Input.
Both units communicate through a proprietary Rosslare protocol,
which provides a secure link between the AYC-x6355 and the
appurtenances. This in turn activates the door lock.
The units also function as the power supply for the AYC-x6355; they
also contain a speaker connection for all sounder abilities.
For more information see the specific Appurtenances Manual.
8.9 Programming the AYC-x6355
Programming the AYC-x6355 is done solely via the unit's keypad
driven Programming Menu System. To reach the Programming Menu
System, the unit must first be put into Programming mode (see
Section 8.9.1).
During a unit’s manufacturing process, certain codes and settings are
pre-programmed. These settings are the called the default factory
settings.
Table 4 shows the names of all the AYC-x6355 controller menus. It
also shows of all the default factory codes and settings for the units.