EasyManua.ls Logo

Saftronics FP5 Series - Page 56

Saftronics FP5 Series
101 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
56 FP5/GP5 User’s Manual
limit, this lower limit value is output as the voltage reference value. The
lower limit value is set in order to prevent stalling at light loads. Set
voltage limits at 6Hz and 60Hz; a value obtained by linear interpolation
should be used to set any limit values other than at 6Hz or 60Hz. Setting
is made as a percentage of motor rated voltage.
Voltage
255V*
n098
n099
Lower Limit
Frequency
6Hz 60Hz
Figure 24 Energy Saving Voltage Lower Limit
* This value is doubled for 460V class inverters.
Chapter 3 - Programming Features
FP5/GP5 Operation
efesotomasyon.com - Control Techniques,emerson,saftronics -ac drive-servo motor

Table of Contents

Related product manuals