8000m Series
- 100 -
BIT3: Output terminal status
BIT4: PID setting value
BIT5: PID feedback value
BIT6: AVI value
BIT7: Reserved
BIT8: Reserved
BIT9: Current step of multi-step speed and
PLC
BIT10: Reserved
BIT11: Counting meter value
BIT12~BIT15: Reserved
While the VFD is in running or stop status, monitoring of status data will be
defined by these parameters which are binary numbers in 16 bits. If any of the
bits is set as 1, the corresponding status data can be selected and monitored by
《 Key. If the bit is set as 0, the corresponding status data cannot be monitored.
Note: Convert binary number into hexadecimal number before setting parameters
of F7.06~F7.08.
Note: Digital input and output terminal status is displayed in decimal number, with
M1(MO1) as the lowest bit. For example, as digit input status is displayed as 3, it
represents M1 and M2 are both closed, with other terminals opened.
F7.09
Inverter module
temperature
0~100℃
F7.10
Inverter software
version
*.**
F7.11
Accumulative running
time
0~9999h
F7.12
Accumulative power-on
time
0~9999h
F7.13 Reserved
These parameters can only be checked and cannot be modified.