- 126 -
0: Alarm and coast to stop. If time span between the current communicating and
last communicating exceeds the setting time of FC.04, VFD will trig an error E016
and coast to stop.
1: No alarm and continue to run. If time span between the current communicating
and last communicating exceeds the setting time of FC.04, VFD will continue
operating.
2: No alarm but stop according to F1.05 (only when F0.01= 2). Under setting of
communication control source, if time span between the current communicating
and last communicating exceeds the setting time of FC.04, VFD will decelerate to
stop.
3: No alarm but stop according to F1.05 (Under all kinds of control command). No
matter what VFD is under any of the keypad control, terminal control or
communication control source settings, as time span between the current
communicating and last communicating exceeds the setting time of FC.04, VFD
will decelerate to stop.
VFD can be set to one of the following methods: shielding the error E016,
stopping or continuing operation, when there are communication malfunctions.
FC.06
Transmission response
action
Factory Setting 00
Setting Options
Unit’s digit:
0: Response to writing
1: No response to writing
Ten’s place:
0:Value not saved when power-off
1: Value saved when power-off
This parameter is for selection of response or not to the host’s message when
communication is carried out between upper monitor and VFD.

Questions and Answers: