EasyManuals Logo

SAJ 8000m Series User Manual

SAJ 8000m Series
153 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #37 background imageLoading...
Page #37 background image
8000m Series
- 36 -
Function
Code
Function Descriptions
Minimum
Unit
Factory
Setting
Modifica-
tion Type
F3.08~F
3.09
Reserved
F3.10
Pre-alarm option
when overload
0: Not detect
1: Effective during running and
keep running after alarm
2: Effective during running
and stop after alarm (fault
code:E023)
3: Effective during constant
running and keep running after
alarm
4: Effective during constant
running and stop after alarm
1
F3.11
Detecting level of
pre-alarm when
overload
1.0~200.0% (referred to inverter
rated current)
0.10% 150.00%
F3.12
Detecting time of
pre-alarm when
overload
0~600s 1s 1s
F4 Group: V/F Control Parameters
F4.00 V/F curve selection
0: Linear curve
1: User-defined curve
2: 1.3 square torque-step-down
curve
3: 1.7 square torque-step-down
curve
4: 2 square torque-step-down
curve
0
F4.01 Torque boost 0.0 %(auto) 0.1%~30.0% 0.10% 1.00%
F4.02
Torque boost
cut-off frequency
0.0~50.0% (relative to motor
rated frequency)
0.10% 20.00%
F4.03 V/F frequency 1 0.00Hz~F4.05 0.01Hz 0.00Hz

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SAJ 8000m Series and is the answer not in the manual?

SAJ 8000m Series Specifications

General IconGeneral
BrandSAJ
Model8000m Series
CategoryController
LanguageEnglish

Related product manuals