8000m Series
- 37 -
Function
Code
Function Descriptions
Minimum
Unit
Factory
Setting
Modifica-
tion Type
F4.04 V/F voltage 1 0.0%~100.0% 0.10% 0.00% ●
F4.05 V/F frequency 2 F4.03~F4.07 0.01Hz 25.00Hz ●
F4.06 V/F voltage 2 0.0%~100.0% 0.10% 50.00% ●
F4.07 V/F frequency 3 F4.05~motor rated frequency 0.01Hz 50.00Hz ●
F4.08 V/F voltage 3 0.0%~100.0% 0.10% 100.00% ●
F4.09
Coefficient of V/F
Slip compensation
0.0%~200.0% 0.10% 0.00% ○
F4.10
Energy-saving
selection
0:Disabled
1:Enabled automatically
0 ○
F4.11 Reserved
F4.12
Low-frequency
threshold of
restraining
oscillation
0~10 2 ○
F4.13
High-frequency
threshold of
restraining
oscillation
0~10 0 ○
F4.14 Reserved
F4.15
Boundary
frequency of
restraining
oscillation
0.00Hz~F0.10 (Maxi.
frequency)
0.01Hz 30.00Hz ○
F4.16 Reserved
F4.17
AVR function
selection
0:Invalid
1:Valid all the time
2: Only invalid during
deceleration
1 ○