057
4.1 Function Code
F8 Group - PID Control Parameters
Function
Code
Name Set Range
Minimum
Unit
Factory
Default
Modi󽗉cation
F8.15
Threshold value of
sleeping
0.0 200.0%
Note: this threshold value is the
percentage of given pressure,
and it is only valid for the 󽗉rst
sleep mode.
0.1% 100.0%
F8.16
Threshold value of
awaking
0.0 200.0%
Note: this threshold value is the
percentage of given pressure.
0.1% 90.0%
F8.17 Delay time of sleep 0.0 3600.0s 0.1s 100.0
F8.18
Delay time of
awaking
0.0 3600.0s 0.1s 5.0
F8.19
Delay time of
adding pump
0.0 3600.0s 0.1s 10.0
F8.20
Delay time of
re d u c i n g pump
0.0 3600.0s 0.1s 10.0
F8.21
Water supply
enabling
(F8.21-F8.24 not
supported by
hardware)
0: disabled
1: PFC enabled
2: SPFC enabled
1 0 ×
F8.22
Delay time
of terminal
disconnect and
connect
0.0 6000.0s 0.1s 0.1
F8.23 Polling time 0.0 6000.0h 0.1h 48.0
F8.24
Lower limit freq. of
reducing pump
0.0 600.00Hz 0.01Hz 0.00
F8.34 Sleep frequency 0.00HZ ~【F0.16】 0.01Hz 0.00 ×

Table of Contents