4.1 Function Code
F8 Group - PID Control Parameters
Function
Code
Name Set Range
Minimum
Unit
Factory
Default
Modication
F8.15
Threshold value of
sleeping
0.0 ~ 200.0%
Note: this threshold value is the
percentage of given pressure,
and it is only valid for the rst
sleep mode.
0.1% 100.0% ○
F8.16
Threshold value of
awaking
0.0 ~ 200.0%
Note: this threshold value is the
percentage of given pressure.
0.1% 90.0% ○
F8.17 Delay time of sleep 0.0 ~ 3600.0s 0.1s 100.0 ○
F8.18
Delay time of
awaking
0.0 ~ 3600.0s 0.1s 5.0 ○
F8.19
Delay time of
adding pump
0.0 ~ 3600.0s 0.1s 10.0 ○
F8.20
Delay time of
re d u c i n g pump
0.0 ~ 3600.0s 0.1s 10.0 ○
F8.21
Water supply
enabling
(F8.21-F8.24 not
supported by
hardware)
0: disabled
1: PFC enabled
2: SPFC enabled
1 0 ×
F8.22
Delay time
of terminal
disconnect and
connect
0.0 ~ 6000.0s 0.1s 0.1 ○
F8.23 Polling time 0.0 ~ 6000.0h 0.1h 48.0 ○
F8.24
Lower limit freq. of
reducing pump
0.0 ~ 600.00Hz 0.01Hz 0.00 ○
F8.34 Sleep frequency 0.00HZ ~【F0.16】 0.01Hz 0.00 ×