063
4.1 Function Code
FA Group - Protective Parameters
Function
Code
Name Set Range
Minimum
Unit
Factory
Default
Modi󽗉cation
FA.12
Overload pre-alarm
level
G type: 20%~ 200% *VFD rated
current 160%
P type: 20%~ 200% *VFD rated
current 120%
1%
Depending
on model
○
FA.13
Overload pre-alarm
delay time
0.0 ~ 300s 0.1s 10.0 ○
FA.14
Temperature
detection threshold
0.0℃~ 90.0℃ 0.1℃ 65.0℃ ×
FA.15
Phase loss
protection of input
and output
0: disabled
1: disabled for input, enabled for
output
2: enabled for input, disabled for
output
3: enabled
1
Depending
on model
×
FA.16
Delay time of input
phase loss protection
0.0 ~ 30.0s 0.1S 1.0 ○
FA.17
Detection reference
of output phase loss
protection
0%~ 100% *VFD rated current 1% 50% ×
FA.18
Detection factor
of output current
imbalance
1.00 ~ 10.00 1.00: imbalance
detection is disabled
Note: detection of output
current imbalance and output
phase loss share the same
reference parameter FA.17 and
fault code E-13.
— 1.00 ×
FA.19 reserved — — 0 ◆
FA.20
PID feedback
disconnection
processing
0: disabled
1: alarm and maintain the
operation at the frequency of
disconnection moment
2: protection action and coast to stop
3: alarm and decelerate to zero-
speed operation according to
preset mode
1 0 ×