4.1 Function Code
FA Group - Protective Parameters
Function
Code
Name Set Range
Minimum
Unit
Factory
Default
Modi󽗉cation
FA.00
Motor overload
protection
0: disabled
1: common motor (electronic
heat relay, with low speed
compensation)
2: variable frequency motor (
electronic heat relay, without
low speed compensation)
1 1 ×
FA.01
Motor overload
protection factor
20.0%~ 120.0% 0.1% 100.0% ×
FA.02
Under voltage
protection
0: disabled
1: enabled (undervoltage is
seen as fault)
1 0 ×
FA.03
Under voltage
protection level
220V: 180 280V 200V
380V: 330 480V 350V
1V
Depending
on model
×
FA.04 Over voltage limit level
220V: 350 390V 370V
380V: 600 780V 660V
1V
Depending
on model
×
FA.05
Voltage limit factor in
decelerating
0 100
0: protection invalid of stall
over voltage
1
Depending
on model
×
FA.06
Current limiting
threshold (only valid
for VF mode)
G type: 80%~ 200% *VFD
rated current 160%
P type: 80%~ 200% *VFD
rated current 120%
1%
Depending
on model
×
FA.07
Current limiting in the
󽗉eld weakening region
0: limited by FA.06
1: limited by conversion
value of PA.06
1 0 ×
FA.08
Current limiting factor
in accelerating
0 100
0: acceleration current
limiting is disabled
1
Depending
on model
×
FA.09
Current limiting in
constant speed running
0: disabled
1: enabled
1 1 ×
FA.10 O󽗈 load detection time 0.1S 60.0s 0.1s 5.0
FA.11 O󽗈 load detection level
0 100%*VFD rated current
0: o󽗈 load detection is
disabled
1% 0%