EasyManua.ls Logo

Sako SKI600 - Page 72

Sako SKI600
180 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
066
4.1 Function Code
FC Group - Advanced Function and Performance Parameters
Function
Code
Name Set Range
Minimum
Unit
Factory
Default
Modi󽗉cation
FC.00 Dynamic braking
0: disabled
1: always enabled
2: only enabled when
decelerating
1 2 ×
FC.01
Initial voltage of
dynamic braking
220V: 340 380V 360V
380V: 660 760V 680V
1V
Depending
on model
FC.02
Hysteresis voltage
of dynamic braking
220V: 10 100V 5V
380V: 10 100V 10V
1V
Depending
on model
FC.03
Action ratio of
d y na mi c br a ki n g
10 100% 1% 100%
FC.04
Restart after power
failure
0: disabled
1: start at start frequency
2: start in speed tracking mode
1 0 ×
FC.05
Restart delay after
power failure
0.0 60.0s 0.1s 5.0 ×
FC.06 Auto reset times
0 100
the setting value of 100 means
unlimited times
1 0 ×
FC.07 Auto reset interval 0.1 6000m 0.1 3.0 ×
FC.08 Cooling fan control
0: auto control mode
1: always running when power on
1 0
FC.09
Password of
operation limiting
function
0 65535
Note 1: the password will take
into e󽗈ect 3 minutes later after
set successfully
Note 2: this parameter cannot be
initialized.
1 0
FC.10
Operation limiting
function
0: disabled
1: enabled
Note: this parameter cannot be
initialized
1 0
FC.11 Limiting time
0 65535(h)
Note: this parameter cannot be
initialized
1 0 ×
FC.12
Freq. decreasing
point of
instantaneous
power failure
220V:180 330V 250V
380V:300 550V 450V
1V
Depending
on model
×

Table of Contents