4.1 Function Code
FC Group - Advanced Function and Performance Parameters
Function
Code
Name Set Range
Minimum
Unit
Factory
Default
Modication
FC.00 Dynamic braking
0: disabled
1: always enabled
2: only enabled when
decelerating
1 2 ×
FC.01
Initial voltage of
dynamic braking
220V: 340 ~ 380V 360V
380V: 660 ~ 760V 680V
1V
Depending
on model
○
FC.02
Hysteresis voltage
of dynamic braking
220V: 10 ~ 100V 5V
380V: 10 ~ 100V 10V
1V
Depending
on model
○
FC.03
Action ratio of
d y na mi c br a ki n g
10 ~ 100% 1% 100% ○
FC.04
Restart after power
failure
0: disabled
1: start at start frequency
2: start in speed tracking mode
1 0 ×
FC.05
Restart delay after
power failure
0.0 ~ 60.0s 0.1s 5.0 ×
FC.06 Auto reset times
0 ~ 100
the setting value of 100 means
unlimited times
1 0 ×
FC.07 Auto reset interval 0.1 ~ 6000m 0.1 3.0 ×
FC.08 Cooling fan control
0: auto control mode
1: always running when power on
1 0 ○
FC.09
Password of
operation limiting
function
0 ~ 65535
Note 1: the password will take
into eect 3 minutes later after
set successfully
Note 2: this parameter cannot be
initialized.
1 0 ○
FC.10
Operation limiting
function
0: disabled
1: enabled
Note: this parameter cannot be
initialized
1 0 ○
FC.11 Limiting time
0 ~ 65535(h)
Note: this parameter cannot be
initialized
1 0 ×
FC.12
Freq. decreasing
point of
instantaneous
power failure
220V:180 ~ 330V 250V
380V:300 ~ 550V 450V
1V
Depending
on model
×