067
4.1 Function Code
FC Group - Advanced Function and Performance Parameters
Function
Code
Name Set Range
Minimum
Unit
Factory
Default
Modi󽗉cation
FC.13
Freq. decreasing factor
of instantaneous
power failure
0: the function of immunity
to transient power failure is
disabled
1 100
1 0
FC.14 Droop control
0.00 10.00Hz
0.00: droop control function is
disabled
0.01Hz 0.00 ×
FC.15
Delay time of rotating
speed tracking
0.1 5.0s 0.1s 1.0 ×
FC.16
Current amplitude
limiting of rotating
speed tracking
80%~ 200% *VFD rated current 1% 100% ×
FC.17
Speed of rotating
speed tracking
1 125 1 25 ×
FC.18 PWM mode
LED one's place: PWM
synthesize method
0: seven segments of full band
1: switch from 7 segment to 󽗉ve
segments
LED ten's place: PWM
temperature correlation
0: disabled
1: enabled
LED hundred's place: PWM
frequency correlation
0: disabled
1: low freq. adjustment, high
Freq. adjustment
2: no adjustment for low freq.,
high freq. adjustment
3: low freq. adjustment, no
adjustment for high freq.
LED thousand's place: 󽗊exible
PWM function
0: disabled
1: enalbed
1 0001 ×

Table of Contents