EasyManua.ls Logo

Sako SKI600 - Page 80

Sako SKI600
180 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
074
4.1 Function Code
FF Group - Factory Parameter
Function
Code
Name Set Range
Minimum
Unit
Factory
Default
Modi󽗉cation
FF.00 Factory Password
0 65535
Note: After password setup was
successful, it will take 3 minutes
to take e󽗈ect
1 0
FF.01 Reserved 0
FF.02 VFD Model
0~30
0: 0.4KW 1: 0.75KW 2: 1.5KW
3: 2.2KW 4: 4.0KW 5: 5.5KW
6: 7.5KW 7: 11KW 8: 15KW
9: 18.5KW 10: 22KW 11: 30KW
12: 37KW 13: 45KW 14: 55KW
15: 75KW 16: 90KW 17: 110KW
18: 132KW 19: 160KW 20: 185KW
21: 200KW 22: 220KW 23: 250KW
24: 280KW 25: 315KW 26: 350KW
27: 375KW 28: 400KW 29: 500KW
30: 630KW
1
Model
Dependant
FF.03 Rated Power
0.4 999.9KW
Note: this parameter can only be
viewed
0.1KW
Model
Dependant
FF.04 Rated Voltage 0 999V 1V 380
FF.05 Rated Current 0.1 6553.5A 0.1A
Model
Dependant
FF.06 Dead Zone Time
3.2 10.0μS
0.4 4.0KW 3.2μS
5.5 22KW 3.5μS
30 110KW 4.0μS
132 630KW 4.5μS
0.1μS
Model
Dependant
FF.07
Software
Overvoltage Point
220V:0 450V 400V
380V:0 850V 800V
1V
Model
Dependant
FF.08
Software
Undervoltage Point
220V:0 280V 150V
380V:0 320V 250V
1V
Model
Dependant
FF.09
Software
Overcurrent Point
50.0 250.0% 0.1% 220.0%
FF.10
Voltage Correction
Factor
80.0 120.0% 0.1% 100.0%
FF.11
Current Correction
Factor
50.0 150.0% 0.1% 100.0%

Table of Contents