7. Installer mode
7.1 DIP switches parameters
To enter installer parameters please follow steps below. Please refer to parameters table description before any changes. Use or buttons to move
up or down between all parameters. Every change/selection conrm by button.
DIP switched are used to set chosen control algorithm. They are under back cover of the thermostat (please refer to the picture below):
DETAILED TABLE WITH ALL INSTALLER PARAMETERS:
Press and hold
TEST / PAIRING
SELECT
SET
+ +
simultanously for about 3 seconds to
enter the installer mode.
Use SELECT button to choose
parameter, conrm selection by SET
button. To change parameter value
use
or buttons and conrm
selection by SET button. To exit the
installer mode, wait 10 seconds -
thermostat will re-turn automatically
to the main screen.
1 2
3 sec
3 sec
3 sec
dxx Function Parameter
Default
value
d01 Temperature display increments 0.1°C or 0.5°C 0.5°C
d02 Temperature oset +/- 3.0°C 0.0°C
d03 Frost Protection setpoint temperature 5.0°C - 17.0°C 5.0°C
d04 Programmer selection 5/2 or 24 hr (7d) 5/2 d
9CPH
±0.25°C
6CPH
Span
TPI
ON
1 2
Type of control TPI Hysteresis
How it works
When TPI is selected on DIP switch № 2, the
DIP switch № 1 is functional. You can choose
the Cycles Per Hour between a lower
comfort level (6CPH) and a higher comfort
level (9CPH).
When Span is selected on DIP switch № 2, the
DIP switch № 1 is not functional. The SPAN
value is set to ± 0.25°C - it is recommended to
use with heating devices.