20 EB 8394 EN
Design and principle of operation
3.3 Travel tables
The M lever is included in the scope of delivery.
Direct attachment to Type3277-5 and Type3277 Actuators
Actuator size Rated travel Adjustment range at positioner Required
lever
Assigned
pin position
[cm²] [mm] Min. Travel Max.
120 7.5 5.0mm to 16.0mm M 25
120/240/350
15 7.0mm to 22.0mm M 35
355/700 30 10.0mm to 32.0mm M 50
Direct attachment to Type2780-2 Actuator
Actuator size Rated travel Adjustment range at positioner Required
lever
Assigned
pin position
[cm²] [mm] Min. Travel Max.
120 6/12 5.0mm to 16.0mm M 25
120 15 7.0mm to 22.0mm M 35
Attachment according to IEC60534-6 (NAMUR)
SAMSON Type3271 Actuator Travel of other valves Required
lever
Assigned
pin position
Size [cm²]
Rated travel
[mm]
Min. Max.
120 7.5 5.0mm 16.0/25.0
1)
mm M 25
120/240/350
15
7.0mm 22.0/35.0
1)
mm M 35
700 7.5
700/355 15/30 10.0mm 32.0/50.0
1)
mm M 50
1)
When 'MAX' is selected as the nominal range (P4 code, see page68)
Attachment to rotary actuators according to VDI/VDE3845
Rotary actuators Required
lever
Assigned
pin position
Min. Opening angle Max.
24° to 100° M 90°
Note