Operating the positioner
7.7 Setting other parameters
The following table lists all the parameter codes and their default settings. Proceed as de-
scribed previously to change parameters.
More details concerning the parameter codes can be found in section11.2.
Parameter codes [default settings]
P0 Status indication P11 End position w > [OFF]
P1 Reading direction P12 Limit A1, min. [2 %]
P2
1)
ATO/ATC [ATO] P13 Limit A2, max. [98 %]
P3
1)
Pin position [35] P14 Display of reference variable w
P4
1)
Nominal range [MAX] P15 INIT Start initialization
P5 Characteristic [0] P16 ZERO Start zero calibration
P6 Reference variable [4 to 20 mA] P17 MAN Manual mode
P7 w/x direction of action [>>] P18 RST Reset
P8
1)
Gain Kp [50] P19 Enable conguration
P9 Pressure limitation 2.3 bar [OFF] P20 Firmware version
P10 End position w < [ON]
1)
Positioner needs to be re-initialized after changing the parameter setting
7.8 Initialization
During initialization the positioner adapts itself optimally to the friction conditions and the
signal pressure required by the control valve.
Risk of injury due to the actuator stem extending or retracting.
Do not touch or block the actuator stem.
The process is disturbed by the movement of the actuator stem.
Do not initialize the positioner while the process is running and only after isolating the plant
by closing the shut-off valves.
WARNING
!
NOTICE
!