EB 8394 EN 53
Operating the positioner
7.4
Entering the air action
− ATO (air to open) applies to a valve opening as the signal pressure increases.
− ATC (air to close) applies to a valve closing as the signal pressure increases.
The signal pressure is the pneumatic pressure at the output of the positioner applied to the
actuator.
Default air action: ATO
Change the air action (enable conguration as described in sec-
tion7.2):
1. Touch
or until Code P2 appears.
2. Press
to conrm selected code. P2 blinks.
3. Touch
or until the required air action appears.
4. Press
to conrm setting.
The changed air action rst becomes effective after the positioner has been re-initialized.
7.5 Entering the direction of action
The direction of action (P7) is set to increasing/increasing (>>) by default, i.e. when the posi-
tioner is initialized, 0
% is displayed when the valve is closed and 100 % when the valve is
fully open. If necessary, the direction of action can be changed (enable conguration as de-
scribed in section7.2):
Changing the direction of action to increasing/decreasing:
1. Touch
or until Code P7 appears.
2. Press
to conrm selected code. P7 blinks.
3. Touch
or until <> appears.
4. Press
to conrm setting.