EasyManua.ls Logo

Samson 3730-3 - Page 69

Samson 3730-3
180 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EB 8384-3 EN 69
Mounting and start-up
5.9.1 Reversing amplier
(1079-1118 or 1079-
1119)
Î RefertoFig.24
1. Mount the connecting plate (6) from the
accessoriesinTable6tothepositioner.
Make sure that both O-rings (6.1) are
seated correctly.
2. Thread the special nuts (1.3) from the ac-
cessoriesofthereversingamplierinto
the boreholes of the connecting plate.
3. Insert the gasket (1.2) into the recess of
thereversingamplierandslideboththe
hollowed special screws (1.1) into the
connecting boreholes A
1
and Z.
4. Placethereversingamplierontothe
connecting plate (6) and screw tight us-
ing both the special screws (1.1).
5. Useascrewdriver(8mmwide)toscrew
theenclosedlters(1.6)intotheconnec-
tion boreholes A
1
and Z.
Air can escape uncontrolled from the signal
pressure connection.
Do not unscrew the sealing plug (1.5) out of
the reversing amplier.
The rubber seal (1.4) is not required and can
be removed when the sealing plug is used.
6. Afterinitialization,setCode16(Pressure
limit) to No.
A
1
1.5 1.6
1.3
6.266.1
1.2 1.1 1 1.6
Z
A
2
1.4
A
1
A
2
Z
A
1
Output 38 Supply 9
Output 38 Supply 9
1.3 1.21.1
From the positioner
Control signals to the actuator
1 Reversingamplier
1.1 Special screws
1.2 Gasket
1.3 Special nuts
1.4 Rubber seal
1.5 Stopper
1.6 Filter
6 Connecting plate
6.1 O-rings
6.2 Screws
Fig.24: Mounting a reversing amplier (1079-1118 or 1079-1119)
NOTICE
!
Note

Table of Contents

Other manuals for Samson 3730-3

Related product manuals