EasyManua.ls Logo

Samson 3730-4 - Status Alarm According to Profile 3.01

Samson 3730-4
100 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5.3 Status alarm according to Profile 3.01
Fault/diagnostic alarm
Value (hex) Status alarm acc. to
Profile 3.01
Operational errors
Device not initialized
0x1C
BAD_OUT_OF_SERVICE
Solenoid valve active
0x80
GOOD_NON_SPECIFIC
Total travel exceeded
0xA4
GOOD_MAINT_REQ
Control loop error
0x4A
GOOD_MAINT_REQ
Zero point error
0xA4
GOOD_MAINT_REQ
Autocorrection
0x80
GOOD_NON_SPECIFIC
Fatal error
0x0C
BAD_DEVICE_FAILURE
No emergency mode
0xA4
GOOD_MAINT_REQ
Reference test aborted
0x80
GOOD_NON_SPECIFIC
Temperature < –40 °C
0x80
GOOD_NON_SPECIFIC
Temperature > 80 °C
0x80
GOOD_NON_SPECIFIC
Initialization errors
x > range
0x80
GOOD_NON_SPECIFIC
Delta x < range
0x80
GOOD_NON_SPECIFIC
Incorrect attachment (mechanics/pneumatics)
0x80
GOOD_NON_SPECIFIC
Initialization time exceeded
0x80
GOOD_NON_SPECIFIC
Initialization/solenoid valve
0x80
GOOD_NON_SPECIFIC
Transit time too short
0x80
GOOD_NON_SPECIFIC
Pin position
0x80
GOOD_NON_SPECIFIC
Initialization running
0x80
GOOD_NON_SPECIFIC
Hardware errors
x signal
0x0C
BAD_DEVICE_FAILURE
i/p converter
0x0C
BAD_DEVICE_FAILURE
Hardware
0x0C
BAD_DEVICE_FAILURE
Data memory
0xA4
GOOD_MAINT_REQ
KH 8384-4 EN 21
Measured value status and valve diagnostics

Other manuals for Samson 3730-4

Related product manuals