DATALOGGER_DS_15 (125)
Storage class: – · Read capability (r)
Test function: Data logger – Data set 1 to 14
Element Parameter name
0 SOLLWERT_W_1 (reference variable w - data set 1)
1 ISTWERT_X_1 (valve position x - data set 1)
2 STELLSIGNAL_Y_1 (drive signal y - data set 1)
3 REGELABWEICH_E_1 (setpoint deviation e - data set 1)
4 ZEIT_T_1 (time t - data set 1)
5 SOLLWERT_W_2 (reference variable w - data set 2)
6 ISTWERT_X_2 (valve position x - data set 2)
7 STELLSIGNAL_Y_2 (drive signal y - data set 2)
8 REGELABWEICH_E_2 (setpoint deviation e - data set 2)
9 ZEIT_T_2 (time t - data set 2)
DEV_REVISION (135)
Storage class: – · Read capability (r)
Revision of the postioner
DEV_REVISION_COMP (134)
Storage class: – · Read capability (r)
Lowest positioner revision with which the device revision (DEV_REVISION) is compatible
DEVICE_DP_STATUS (126)
Storage class: – · Read capability (r)
Current status of the PROFIBUS-DP state machine
The state machine runs through the following states during the transition to cyclic data exchange:
Wait prm: Parameterization telegram not yet received
Wait cfg: Configuration telegram not yet received
Data exchg: Cylic data exchange taking place
This information serves to pinpoint problems.
DEVICE_PRODUCT_NUM (51)
Storage class: S · Read/write capability (r/w) · Supported modes: ALL
Product number of the positioner.
DIAG_EVENT_SWITCH_2 (61)
Storage class: S · Read/write capability (r/w) · Supported modes: ALL
KH 8384-4 EN 49
Physical Block, Slot 0 · Manufacturer-specific parameters