7 · Calibration sequence mixed up
8 to10 · –
11 · Timeout
12 · Proportional range restricted too much
13 · Rated travel or transmission incorrectly selected
14 · Mechanics system stuck (during initialization)
15 · Pneumatics system leaks (during initialization)
16 · Action interrupted as a production test has not yet been performed successfully
17 · Initialization status: Mechanical stops determined
18 · Initialization status: Minimum control pulse determined
19 · Initialization status: Minimum transit times determined
20 · Initialization canceled by activation of the solenoid valve
21 to 29 · –
30 = Zero point error
31 to 253 · –
254 = Successful
255 = No valid data from the closed-loop control
SERVO_GAIN_1 (115)
Storage class: S · Read/write capability (r/w) · Supported modes: ALL
K
P
step (Code 17)
[7]
SERVO_RATE_1 (116)
Storage class: S · Read/write capability (r/w) · Supported modes: ALL
T
V
step (Code 18)
[2]
SETP_CUTOFF_DEC (118)
Storage class: S · Read/write capability (r/w) · Supported modes: ALL
Final position w < (Code 14)
If the reference variable falls below the entered value, the valve moves towards the final position which
corresponds to 0 % reference variable.
Electropneumatic actuators are completely filled with air or vented (depending on the fail-safe position).
[0.0 %]
KH 8384-4 EN 73
AO Transducer Block, Slot 1 · Profile-specific parameters