Parameter WE Adjustment range
Vorlauftemp.-Sollwert
(flow temp. set point)
65 °C 20 to 120 °C
6.4 Time schedules
Two times-of-use can be programmed for each day of the week.
The times-of-use can be entered individually for each day of the week or together for all days of
the week (Monday to Sunday).
Note: The programming of times-of-use and public holidays are described in detail in section
1.7.
2
[Übersicht > Parameter > Warmwasserbereitung]
Parameter WE Adjustment range
Nutzungszeiten
(times-of-use)
7:00 to 22:00 As required
EB 5571-2 EN 35
Functions of DHW heating