9.1.3 DHW heating
2
[Übersicht > Parameter > Warmwasserbereitung]
Parameters Adjustment
range
WE Comments
Vorlauftemp.-Sollwert
(flow temp. set point)
20 to 120 °C 65 °C
Flow temperature set point for DHW demand
Speicher min
(min. storage tank)
20 to 90 °C 40 °C Activation value for storage tank charging
Speicher max
(max. storage tank)
20 to 90 °C 45 °C Dectivation value for storage tank charging
Desinfektionstemp.
(disinfection temp.)
50 to 80 °C 70 °C
Storage tank temperature set point for thermal
disinfectio
NZ therm. Desinfektion
(times-of-use for
thermal disinfection)
Note: Only with active storage tank sensors!
Montag - Sonntag
(Mon - Sun)
As required
7.00 to
22.00 h
Block entry for all days of the week
Montag (Mon)
Separate entry for each day of the week
NOTE!
The block entry writes over all times-of-use pro
-
grammed separately for a day of week.
Dienstag (Tue)
Mittwoch (Wed)
Donnerstag (Thurs)
Freitag (Fri)
Samstag (Sat)
Sonntag (Sun)
Vorrangschaltung
(priority operation)
EIN (on),
AUS (off)
AUS Priority of DHW heating
Nutzungszeiten (times-of-use)
Montag - Sonntag
(Mon - Sun)
As required
7.00 to
22.00 h
Block entry for all days of the week
Montag (Mon) Separate entry for each day of the week
NOTE!
The block entry writes over all times-of-use pro
-
grammed separately for a day of week.
Dienstag (Tue)
Mittwoch (Wed)
EB 5571-2 EN 79
Appendix