Parameter WE Adjustment range
Regelkreis (control circuit)
= stetig (continuous)
3-Punkt Continuous, three-step
2
[Übersicht > Parameter > Wärmetauscher 1…3]
Parameters WE Adjustment range
Kp 1.0 0.1 bis 99.9
Tn 30 s 0 bis 999 s
Tv 0 s 0 bis 999 s
Ty 45 s 15 bis 600 s
Heating circuits HK1 to HK3
The continuous signal is issued by the following binary outputs:
4
AA6 at ModBus I/O 1402-0328 (1) for heating circuit HK1
4
AA6 at ModBus I/O 1402-0328 (2) for heating circuit HK2
4
AA6 at ModBus I/O 1402-0328 (3) for heating circuit HK3
Note: Alternative assignment is shown in section 8.1.
2 [Übersicht > Service > Heizkreis 1…3]
This menu can only be selected after the application key number has been entered!
Parameter WE Adjustment range
Regelkreis (control circuit)
= stetig (continuous)
3-Punkt Continuous, three-step
2
[Übersicht > Parameter > Heizkreis 1…3]
Parameters WE Adjustment range
Kp 6.0 0.1 to 99.9
Tn 120 s 0 to 999 s
Tv 0 s 0 to 999 s
Ty 120 s 5 to 600 s
EB 5571-2 EN 41