Parameters Adjustment range WE Comments
Montag - Sonntag
(Mon - Sun)
As required
7.00 to
22.00 h
Block entry for all days of the week
Montag (Mon)
Separate entry for each day of the week
NOTE!
The block entry writes over all
times-of-use programmed separately for a
day of week.
Dienstag (Tues)
Mittwoch (Wed)
Donnerstag (Thurs)
Freitag (Fri)
Samstag (Sat)
Sonntag (Sun)
Feiertage (public holidays) As required
St.-Nr. (ext. Bedarf)
St. no. (external demand)
AUS, 5 to 999 AUS
Address of station, from which the ex
-
ternal set point for transfer over Modbus
is given
Begrenzung Xw Auf (°C)
(limit Xw OPEN)
AUS, 2 to 10 °C AUS
Attenuation intensity for the condensate
accumulation control
Separater Sollwert
(separate set point)
EIN (on), AUS (off) AUS
Activation/input of the fixed set point
Sollwert Anf.
Sollwert Anf.
(set point demand)
20 to 120 °C 65 °C
Vorlaufgrenzwert
(flow limit)
20 to 120 °C 55 °C
Flow temperature limit under which pump
lag time is ended.
Außentemperatur senden
St.-Nr.
(send outdoor temp.)
1)
AUS, 5 to 255 AUS
Rücklaufbegrenzung
(return flow limit)
1)
0.1 to 2.0 0.1
Externer Bedarf (0V)
(external demand)
1)
0 to 150 °C 0 °C
Range for external demand during
transfer over an analog signal to UE2
Externer Bedarf (10V)
(external demand)
1)
0 to 150 °C 120 °C
1)
Firmware version 1.50 and higher
EB 5571-2 EN 83
Appendix