20 KA 5578-E EN
Operation
5.3 Entering day and night set points
The day set points apply during day mode (rated operation) and during times-of-use pro-
grammed for automatic mode.
The night set points apply during night mode (reduced operation) and outside the times-of-
use programmed for automatic mode.
The desired room temperature for the day and night set points can be programmed.
Switch position
Parameters WE Value range
HC1 room temperature 20.0°C 0.0 to 40.0°C
HC2 room temperature 20.0°C 0.0 to 40.0°C
HC3 room temperature 20.0°C 0.0 to 40.0°C
HC11 room temperature 20.0°C 0.0 to 40.0°C
HC12 room temperature 20.0°C 0.0 to 40.0°C
HC13 room temperature 20.0°C 0.0 to 40.0°C
DHW temperature 60.0°C Min. to max. DHW temperature
HC1 OT deactivation value 22.0°C 0.0 to 50.0°C
HC2 OT deactivation value 22.0°C 0.0 to 50.0°C
HC3 OT deactivation value 22.0°C 0.0 to 50.0°C
HC11 OT deactivation value 22.0°C 0.0 to 50.0°C
HC12 OT deactivation value 22.0°C 0.0 to 50.0°C
HC13 OT deactivation value 22.0°C 0.0 to 50.0°C
Switch position
Parameters WE Value range
HC1 room temperature 15.0°C 0.0 to 40.0°C
HC2 room temperature 15.0°C 0.0 to 40.0°C
HC3 room temperature 15.0°C 0.0 to 40.0°C
HC11 room temperature 15.0°C 0.0 to 40.0°C
HC12 room temperature 15.0°C 0.0 to 40.0°C
HC13 room temperature 15.0°C 0.0 to 40.0°C
DHW temperature 40.0°C Min. to max. DHW temperature