Piping Diagram
Temperature Compensation
▪ Purpose
Compensate for variances in temperature affecting people differently in the room. Wind chill is caused by indoor tempera-
▪ Concept
If measuring the indoor temperature using the internal temp sensors on indoor units in heating mode, the temperature is
and the temperature difference is equivalent to the compensation temperature.
▪ Control specifications in detail
Factory default (product option code SEG6)
△ T* = 5 K
- others : △ T* = 2 K
Installation setting( installation option code SEG21)
SEG21 Setting
△ T*
0 Factory default
1 2 K
2 5 K
* △ T : Heating compensation temperature
In case of using external room temp. sensor
( Installation option SEG4 = 1 ) :
△
T = 0
▪ Notes
- Order of priority : Use of external temp sensor > Install offset > Basic option.
7-3 Functions (cont.)