Piping Diagram
Samsung Electronics 265
Fan Control in Thermo-Off Condition
Purpose

Concept

fans turn on by default under the same condition.

If the options are not changed, fans turn on or off by default according to the status under the same condition.
Control specifications in detail
Condition(s) required to use the mode : Install options are changed

Mode Thermo EEV Fan "02" SEG4 setting
Cooling
ON Open On all
OFF
Closed
(0 or 35)
On 0,1,2,3
Off 4,5,6,7
Heating
ON Open On all
OFF
Open
in 120step
Off & On (20℃↑ ) 0,4
Off & On
(20℃↑ , 20 sec on every 5 min)
2,6
Off 1,3,5,7
"2" SEG 4 External room sensor 
0 Disuse Disuse
1 Use Disuse
2 Disuse Use-Heating
3 Use Use-Heating
4 Disuse Use-Cooling
5 Use Use-Cooling
6 Disuse Use-Both
7 Use Use-Both