E-12
1(L)
2(N)
Vc Vc Vw Vw F1 F2 V1 V2 F3 F4
F1 F2
Receiver
& Display
Unit(Optional)
Float
SwitchDrain
Pump(Optional)
Wired Remote
Controller
MAIN PCB
Power
1
ø,
220- 240V~, 50H
z
MAIN POWER
Indoor Unit
Outdoor Unit
Cable Specifications
Wiring Diagram
Communication
Connecting the Connection Cord(Continued)
Single Phase
Power supply Max/Min(V)
MCCB ELB
Power cable length Earth cable
220-240V~/50Hz 264/198 Trip:25A 25A 2.5mm,2wires 10m or less Ø1.6mm,1wire
The power cables are not supplied with the air conditioner.
The power cables use the grade H07RN-F or H05RN-F materials.