Drain Hose Installation
Wrap the drain hose with the insulation drain as shown in figure and secure it.
3
Install the drain hose so that its length can be as short as possible.Internal
diameter of the drain hose should be the same or slightly biggerthan the
external diameter of the drain hose port.
Inner diameter of the drain hose
2
Give a slightly slant to the drain hose for proper drainage of
condensate.
Fix the flexible hose to the PVC with the supplied cable ties-
ecurely.
Note
32mm(Inner diameter)
CAUTION
Must fit tightly againstbody
without any gap.
Insulation cover drain
No gap
Insulation drain hose
Cable-Tie
Indoor
Unit
Care must be taken when installing the drain hose for the indoor
unitto ensure that any condensate water is correctly drained outside.
Thedrain hose can be installed to the right of the base pan.
Insert the flexible hose to the drain hose port.
1
Fix the flexible hose to the indoor unit with the supplied
cableclamp securely.
(Use the screwdriver to fix the flexible hose securely.)
Note
Cable
Clamp
CAUTION
Do not apply force to the piping on the unit side
when connecting the drain hose. The hose should
not be allowed to hang loose from its connection to
the unit. Fasten the hose to a wall, frame or other
support as close to the unit as possible.
When not installing the drain pump
Do not give the hose and upward gradient
after the connection port.
This will cause water to flow backwards when
the unit is stopped, resulting in water leaks.
When installing the drain pump
If it is necessary to increase the height of the
drain hose somewhat, the portion directly after
75cm. If it is raised higher than 75cm, there can
be water leaks.
Ceiling
75cm or less
Upward gradien
Ceiling
Support pieces
Ceiling