26 S&C Instruction Sheet 695-535
Trip Mode, Interrupter 1 and Interrupter 2
The Trip Mode setting congures the interrupting setting for the available interrupting
ways (Interrupter 1 and Interrupter 2) of the overcurrent control. Vista SD switchgear is
only available in the Three-Phase Trip/Three-Phase Lockout trip mode.
NOTICE
Vista SD Underground Distribution Switchgear is not available with Single-Phase
Trip/Single-Phase Lockout or Single-Phase Trip/Three-Phase Lockout trip
modes. Only select the Three-Phase Trip/Three-Phase Lockout mode.
STEP 1. To congure the Trip mode, select a Trip mode from the Trip Mode menu:
Select the Three-Phase Trip/Three-Phase Lockout mode. See Figure 20.
When the Three-Phase Trip/Three-Phase Lockout setting is selected, the
Time Overcurrent Phase Protection settings in the interrupter page are
configured using the settings listed under Phase B. All three gang-operated
phases will trip and lock out in response to an event.
STEP 2. Click on the Save button and check for success conrmation message.
Programming the Control Settings
Figure 20. Select the Trip Mode setting for Interrupter 1 and Interrupter 2 from the Global Settings
Menu.