3-60
Control of W-2WAY ECO-i SYSTEM
1
2
3
4
5
6
7
8
4. System Controller
(b) Zone registration using the system controller (SHA-
KC64AG)
In this case, you set all Central addresses by system
controller at once manually.
(1) Press the
and buttons at the same time for
more than 4 seconds.
and CODE No. C1 will flash.
(2) After confirming that CODE No. C1 is displayed, press the
button. Once in this mode, a change takes place as
shown in Fig. 3-43.
(3) Select the zone and group No. which you want to set with
and (GROUP) buttons. If already
set, press the
button.
(4) Set the unit No. (Indoor unit address) with
and
buttons, according to the zone registration table.
R.C. No. ..........................
button
Indoor unit No..................
button
(5) Press the
button.
GROUP No. turns ON and UNIT No. (Indoor unit address)
changes from flashing to ON state. UNIT No. is registered
to selected ZONE No. and GROUP No.
If you make a mistake, then press the
button and
reselect the ZONE, GROUP and UNIT No.
(6) Register the other UNIT Nos. in the same way by follow
-
ing steps (3) to (5).
(7) Finally, complete the registration by pressing the
but-
ton.
flashes for a few minutes, then goes OFF.
(c) Automatic zone registration using the system con
-
troller (SHA-KC64AG)
(1) Press the
and buttons at the same time for
more than 4 seconds.
and CODE No. C1 will flash.
(2) Select CODE. No. C2 by pressing
and
button and press the button.
C2 changes from flashing to ON state and automatic
zone registration will start.
(3) All registered GROUP Nos. will disappear.
(4) Central addresses will be assigned from small indoor unit
addresses to large addresses in numerical order auto-
matically.
After automatic zone registration is completed,
changes from flashing to OFF.
(5) If an error occurs "CHECK" starts flashing and zone reg
-
istration finishes at this time. Press the
button.
(6) Finally, complete automatic zone registration mode by
pressing the
button.
flashes for a few minutes, then goes OFF.
Selected
group No. if
no data is
registered.
If no data is
registered
no number
is displayed.
If data is
registered
the unit No.
is displayed.
Fig. 3-43
Fig. 3-44
For example, in the case at left
Zone 3, group No. 7
Unit No. (indoor unit address) 2-8
Unit No. 2-8 is registered to zone 3-group 7.
Fig. 3-45