Design of W-2WAY ECO-i SYSTEM Unit Specifications
1
2
3
4
5
6
7
8
3. Electrical Wiring
3-1. General Precautions on Wiring
(1) Before wiring, confirm the rated voltage of the unit
as shown on its nameplate, then carry out the wiring
closely following the wiring diagram.
(2) Provide a power outlet to be used exclusively for
each unit, and a power supply disconnect and circuit
breaker for overcurrent protection should be provided
in the exclusive line.
(3) To prevent possible hazards from insulation failure,
the unit must be grounded.
(4) Each wiring connection must be done in accordance
with the wiring system diagram. Wrong wiring may
cause the unit to misoperate or become damaged.
(5) Do not allow wiring to touch the refrigerant tubing,
compressor, or any moving parts of the fan.
(6) Unauthorized changes in the internal wiring can be
very dangerous. The manufacturer will accept no re-
sponsibility for any damage or misoperation that occurs
as a result of such unauthorized changes.
(7) Regulations on wire diameters differ from locality to
locality. For field wiring rules, please refer to your LOCAL
ELECTRICAL CODES before beginning.
You must ensure that installation complies with all rel-
evant rules and regulations.
(8) To prevent malfunction of the air conditioner caused by
electrical noise, care must be taken when wiring as fol-
lows:
The remote control wiring and the inter-unit control wiring
should be wired apart from the inter-unit power wiring.
Use shielded wires for inter-unit control wiring between
units and ground the shield on both sides.
(9) If the power supply cord of this appliance is damaged,
it must be replaced by a repair shop appointed by the
manufacture, because special purpose tools are re-
quired.
3-2. Recommended Wire Length and Wire Diameter for Power Supply System Outdoor unit
Outdoor unit
(A) Power supply
Time delay fuse or
circuit capacity
or
(A) Power supply
Time delay fuse or
circuit capacity
Wire size Max. length Wire size Max. length
SPW-C0705DXHN8 4 mm² 60 m 25 A 4 mm² 60 m 25 A
SPW-C0905DXHN8 6 mm² 71 m 30 A 6 mm² 71 m 35 A
SPW-C1155DXHN8 6 mm² 58 m 35 A 6 mm² 58 m 35 A
SPW-C1305DXHN8 10 mm² 79 m 40 A 10 mm² 79 m 50 A
SPW-C1405DXHN8 10 mm² 68 m 50 A 10 mm² 68 m 50 A
Indoor unit
Type
(B) Power supply
Time delay fuse or
circuit capacity
2.5 mm²
K Max. 150 m 10 – 16A
AD, LD, S, X, T, U, F, FM Max. 130 m 10 – 16A
D (254, 364, 484) Max. 60 m 10 – 16A
D (764/964) Max. 50/30 m 10 – 16A
GU055XH Max. 85 m 10 – 16A
GU075XH Max. 65 m 10 – 16A
GU105XH Max. 60 m 10 – 16A
Control wiring
(C) Inter-unit (between outdoor and indoor
units) control wiring
(D) Remote control wiring (E) Control wiring for group control
0.75 mm² (AWG #18)
Use shielded wiring*
0.75 mm² (AWG #18)
Use shielded wiring
0.75 mm² (AWG #18)
Use shielded wiring
Max. 1,000 m Max. 500 m Max. 500 m (Total)
(F) Inter-outdoor unit control wiring
0.75 mm² (AWG #18)
Use shielded wiring
Max. 500 m
* With ring-type wire terminal.
NOTE