W-2WAY ECO-i SYSTEM Unit Specifications
1
2
3
4
5
6
7
8
2. Indoor Unit
2-1. Specifications
Unit Specifications
MODEL NAME Heat Recovery with Direct-expansion Coil
MODEL No. SPW-GU055XH
POWER SOURCE 220 - 230 - 240 V / single-phase / 50 Hz
PERFORMANCE Cooling Heating
Capacity
Total kW 4.71 5.58
Expansion Coil kW 2.8 3.2
Total heat
exchanger
Enthalpy exchange efficiency
Summer(%) 58
Winter(%) 66
Temperature exchange % 73
Air circulation (High at 230 V) M
3
/ h 500
Moisture removal (High) Liters / h 2.2 –
External Static
Pressure
Air Charge Pa 183
Air Discharge Pa 205
ELECTRICAL RATINGS
Voltage rating V 220 230 240 220 230
240
Available voltage range V 198 - 264 198 - 264
Running amperes A 2.5 2.4 2.3 2.5 2.4
2.3
Power input kW 0.532 0.532 0.532 0.532 0.532
0.532
Power factor % 96 96 96 96 96
96
Starting amperes A 8.2
FEATURES
Heat exchanger
Direct-Expansion Coil: Plate finned tube
Total heat exchanger: Static conversion
Controls Microprocessor
Fan speeds High, (Low*)
Air filter
Air Charge Long-life filter (Washable)
Air Discharge Long-life filter (Washable)
Refrigerant control Electronic Expansion Valve
Operation sound dB - A 50
Refrigerant tubing connections Flare type
Refrigerant tube
diameter
Liquid tube mm (in.) 6.35 (1/4)
Gas tube mm (in.) 12.7 (1/2)
Drain connection 25A (Connection port R1 screw)
Drain pump –
Duct connection port mm ø 250 × 4
Timer Remote Controller Optional (RCS-TM80BG)
High performance filter Optional (65% colorimetric)
Humidifier Optional (natural evaporating type)
Supplied accessories
External static pressure line switching connector,
Insulation, Clamper, Installation and Operating Manual.
DIMENSIONS & WEIGHT
Unit dimensions
Height mm 425
Width mm 1,785
Depth mm 1,000
Net weight kg 155
Rated conditions
• (Low*): When the supplied external static pressure line switching connector is connected.
• The numerical value within the parenthesis of fresh air conditioning load throughput is value of the heat recovery amount due to total heat
exchange.
• As for the Direct-Expansion Coil efficiency, when it is run under the test conditions stated below
Cooling: Direct-Expansion Coil port temperature 27 °C DB and 19 °C WB (discharge air), Outdoor air inlet temperature 35 °C DB and 24 °C
WB (charge air).
Heating: Direct-Expansion Coil port temperature 20 °C DB (discharge air), Outdoor air inlet temperature 7 °C DB and 6 °C WB (charge air)
• Efficiency of the total heat exchanger depends on the following conditions.
Summer: Indoor temperature 27 °C DB & 20 °C WB (discharge air), Outdoor temperature 35 °C & DB 29 °C WB (charge air).
Winter: Indoor temperature 20 °C DB & 14 °C WB (discharge air), Outdoor temperature 5 °C & DB 2 °C WB (charge air).
• The operation sound is measured when the unit is connected to the duct and operated in the anechoic room, associated with the value
measurement directly 1.5m from under the unit.
Once true installation effects taken into account, the actual levels will exceed the indicated values due to reflections off adjacent surfaces and
peripheral noise.
• The changes of H/L of external static pressure depend on the plug equipped connector. However, it will not affect the remote control indication
and will display the HIGH mark.
• This unit has no solvent resistance. Please pay attention to the installation site.