4-12
W-2WAY ECO-i SYSTEM Unit Specifications
1
2
3
4
5
6
7
8
1. Outdoor Unit
Unit Specifications (11)
MODEL NAME
W-2WAY ECO-i Capacity Control Outdoor Unit <34 horsepower>
GENERAL MODEL No.
SPW-WC3405DXHN8
COMPONENT OUTDOOR UNIT
SPW-
C1305DXHN8
SPW-
C0905DXHN8
SPW-
C0905DXHN8
POWER SOURCE
380 - 400 - 415 V / 3N / 50 Hz 380 - 400 - 415 V / 3N / 50 Hz 380 - 400 - 415 V / 3N / 50 Hz
PERFORMANCE
Cooling capacity kW (BTU / h) 96.0 (327,600)
Heating capacity kW (BTU / h) 108.0 (368,500)
COP
Cooling standard – 3.50
Heating standard – 4.00
Heating / Cooling ave.
– 3.75
UNIT DIMENSIONS
Height mm (in.) 1887 (74
-
9 / 32)
Width mm (in.) 2870 (112-1 / 1)
Depth mm (in.)
890 (Ceiling dimension) (+60)
(35-1 / 32) (+2 - 3 / 8)
Net weight kg (lbs.) 345 (760) 295 (650) 295 (650)
Color (Munsell code) Silky shade (1Y 8.5 / 0.5)
ELECTRICAL RATINGS
Voltage rating V 380 400 415
Cooling
Running amperes A 45.4 43.1 41.6
Power input kW 27.4 27.4 27.4
Power factor % 92 92 92
Heating
Standard
Running amperes A 44.7 42.5 41.0
Power input kW 27.0 27.0 27.0
Power factor % 92 92 92
Low temp.
Power input kW 30.0 30.0 30.0
Starting amperes A 103 104 106
COMPRESSOR
Type - Q'ty Hermetic type x 3 Hermetic type x 2 Hermetic type x 2
Motor output kW 3 + 3.75 x 2 3 + 3.75 3 + 3.75
Refrigeration oil
Type FV68S (Ether oil)
Charge amount L 5.9 4.9 4.9
Crankcase heater W 25 + 32 x 2 25 + 32 25 + 32
Capacity control % –
Refrigerant amount at shipment
kg R410A - 13.0 R410A - 12.0 R410A - 12.0
Refrigerant control
Electronic expansion valve
Defrost method
Reverse-cycle defrost, outdoor unit cycle defrost
Heat exchanger
Tube with plate fins
FAN DEVICE
Type - Q'ty Propeller fan x 1 Propeller fan x 1 Propeller fan x 1
Air circulation m
3
/ min 200 160 160
External static pressure Pa 0 0 0
Motor output (No. of poles) kW 0.7 (8P) 0.7 (8P) 0.7 (8P)
Protective devices High pressure switch, overcurrent (CT method)
TUBING
Refrigerant tubing
Gas tube mm (in.)
ø25.4 (1) (Brazing) ø22.22 (7 / 8) (Brazing)
Liquid tube mm (in.)
ø12.7 (1 / 2) (Flare nut) ø9.52 (3 / 8) (Flare nut)
Balance tube mm (in.)
ø6.35 (1 / 4) (Flare nut)
Drain port
–
External air temperature operation range °C Cooling: -10 ~ 43 °C (DB) Heating: -20 ~ 15 °C (WB)
Operation sound (Hi) dB-A
63.0 (Quiet mode: 60.0)
Primary accessories None
Connection tubing
(ø22.22)
Connection tubing
(ø22.22)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
* Performance, electrical characteristics values and operating sound are based on JIS B8616 package A/C.
(Cooling: Indoor intake air temp. 27°C DB / 19°C WB. Outdoor intake air temp. 35°C DB.)
(Heating [standard]: Indoor intake air temp. 20°C DB. Outdoor intake air temp. 7°C DB / 6°C WB.)
(Heating [low temp.]: Indoor intake air temp. 20°C DB / 15°C WB or less. Outdoor intake air temp. 2°C DB / 1°C WB.)