Control of W-ECO MULTI SYSTEM
3
TD831077
III - 3
1. Main Operating Functions
Heating operation control
1 During heating operation, the “Set fan speed”
is set as follows after the thermostat turns ON.
2 The following control takes place after reaching
the set fan speed.
E2 Temp
Auto
LL
L
Me
H (moves to control 2 )
moves to control 2
Set
fan
speed
Me
H
L
Stopped
or LL
E2 Temp
Auto
H
Me
H
H
Me
L
Me
L
Me
L
1-3. Auto flap control
[Applicable indoor units]
4-Way, 2-Way, & ceiling mounted
The airflow direction can be set at 5 stages with
FLAP setting button.
Flap position according to the operating state
4-Way Ceiling
2-Way mounted
Fan Initial setting F2 F1
Manual setting F1 ~ F5
Cooling, dry Initial setting F2 F1
Manual setting F1 ~ F3
Heating Initial setting F4
(H / Me) Manual setting F1 ~ F5
Heating Initial setting F4
(L) Manual setting F1 ~ F4
Sweep F1 ~ F5
Heating
stand by
F2
When stopped F5
* Movement of flap
When changing from F4 to F3
moves once through F5 & F1,
and then set at F3.
(F4 = F5 = F1 = F2 = F3)
E2: Indoor coil temp.
NOTE
33
31
27
25
1016_1143
43
41
38
1017_1143
F1
636_8132
F2
F3
F4
F5
Flap position