COOLING
Model Number : STW0633C2 / 0634C2
Indoor Unit Outdoor Unit Complete Unit
Fan Motor Fan Motor Compressor
Performance at 265V, 1-phase 60Hz
Rating conditions Running amps. A 0.09 0.32 1.99 2.4
Power input kW 0.025 0.085 0.500 0.61
Full load conditions Running amps. A 0.09 0.32 2.49 2.9
Power input kW 0.025 0.085 0.630 0.74
Model Number : STW0933C2 / 0934C2
Indoor Unit Outdoor Unit Complete Unit
Fan Motor Fan Motor Compressor
Performance at 265V, 1-phase 60Hz
Rating conditions Running amps. A 0.09 0.32 2.69 3.1
Power input kW 0.025 0.085 0.690 0.80
Full load conditions Running amps. A 0.09 0.32 3.39 3.8
Power input kW 0.025 0.085 0.870 0.98
Model Number : STW1233C2 / 1234C2 / 1235C2
Indoor Unit Outdoor Unit Complete Unit
Fan Motor Fan Motor Compressor
Performance at 265V, 1-phase 60Hz
Rating conditions Running amps. A 0.15 0.38 3.67 4.2
Power input kW 0.040 0.100 0.960 1.10
Full load conditions Running amps. A 0.15 0.38 4.77 5.3
Power input kW 0.040 0.100 1.240 1.38
Model Number : STW1534C2 /1535C2
Indoor Unit Outdoor Unit Complete Unit
Fan Motor Fan Motor Compressor
Performance at 265V, 1-phase 60Hz
Rating conditions Running amps. A 0.15 0.38 5.27 5.8
Power input kW 0.040 0.100 1.350 1.49
Full load conditions Running amps. A 0.15 0.38 6.77 7.3
Power input kW 0.040 0.100 1.720 1.86
Rating Conditions : Indoor Air Temperature 80°F (26.7°C) D.B. / 67°F (19.4°C) W.B.
Outdoor Air Temperature 95F (35°C) D.B.
Full Load Conditions : Indoor Air Temperature 80°F (26.7°C) D.B. / 67°F (19.4°C) W.B.
Outdoor Air Temperature 115°F (46.1°C) D.B.